Skip to content
Saha

Compressors, pressure vessels, booster sets and forklifts: operator checks and statutory inspections

Keeping a mixed equipment fleet in order: daily operator checks, pressure vessel and lifting equipment inspections in Turkey, hydrostatic and load tests, meters and one template for all of it.

· 8 min read

Illustration of an air compressor with its receiver, a forklift and an inspection calendar with one date marked in orange

Walk into the plant room of a logistics warehouse: a screw compressor with a 500-litre air receiver, a booster set, a closed expansion tank in the corner. Out in the warehouse there are six forklifts, a lifting table at the dock and a hoist in the loading bay. Each is looked after by a different service company, each one’s maintenance sits in a different logbook, and the yearly inspection reports live in a ring binder. When an inspector asks “when was the last load test on the forklifts?”, the answer takes an afternoon.

This guide covers how to keep maintenance and statutory periodic inspections for a mixed fleet like that in one routine: the operator’s daily check, the service company’s maintenance and the authorised inspector’s periodic inspection. They are three different jobs and should be recorded separately.

1. Three jobs: operator, maintenance, inspection

  • Pre-use operator check. The short visual check and function test the person at the controls of a forklift or crane does on every working day.
  • Maintenance. The work you or your service company do: oil, filters, belts, the safety valve, cleaning. How often usually comes from the manufacturer and from practice.
  • Periodic inspection. A statutory check by an authorised person, documented in a report. It gives an opinion on whether the equipment is fit for use.

Closing a maintenance work order does not mean the inspection was done, and an inspection report does not replace maintenance.

2. What the regulation says, briefly

In Turkey, periodic inspections of work equipment are governed by the regulation on health and safety in the use of work equipment (mevzuat.gov.tr). For the equipment in this guide, the main points you can verify are:

  • Pressure vessels (Annex III, Table 1): steam and superheated water boilers, heating boilers, compressed air and gas tanks including compressor air receivers, closed expansion tanks, calorifiers and storage tanks, steam cooking kettles and autoclaves have a maximum interval of one year. A hydrostatic test at the test pressure of the manufacturing standard (or 1.5 times the working pressure when there is none) is done at least every three years and after a major repair.
  • Lifting and conveying equipment (Annex III, Table 2): cranes, hoists, industrial trucks including forklifts and pallet trucks, vehicle lifts, lifting tables, conveyors and slings have a maximum interval of one year. A load test with a factor of 1.25 static (1.5 for manually operated equipment) and 1.1 dynamic is done at least every three years. Lifts covered by the Lift Regulation fall under separate rules.
  • Who inspects. Engineers, technical teachers or technicians of the relevant branch, all registered in EKİPNET. For pressure vessels and lifting equipment that is the mechanical group (for pressure vessels, chemical and aeronautical engineers are listed too). The contract for the inspection is registered in İSG-KATİP at least one day in advance.
  • Operator checks. The operator does a visual check before use and records it. If a defect is found, the equipment is taken out of use and sent for a periodic inspection.
  • Defects and records. Defects are minor or major; equipment with a major defect is not operated. Maintenance and repair records are kept for the whole service life of the equipment, and inspection reports for as long as it is in use.
  • Equipment not in the tables. Where neither the tables nor a standard give an interval, the manufacturer’s recommendation applies, then a risk assessment; the maximum interval in the tables can never be exceeded.

Settle which inspections apply to your equipment with your occupational safety specialist and the inspection company. Whether a booster set’s pressure tank needs its own inspection, for example, depends on the type of tank.

3. The daily operator check: three minutes, on record

In most companies the forklift driver does a morning check, but nobody writes it down. The regulation asks for a record. Keep the check short:

  • No cracks, deformation, wear or corrosion
  • Connections tight
  • Functions tested: brakes, lift, emergency stop, horn
  • Photo if there is a defect

Four items, three minutes. Two things matter: that every working day leaves a record on the equipment itself, and that “nothing was recorded today” shows up. When an item fails, the driver does not use the truck and reports it; the truck is marked as out of order and sent for a periodic inspection.

4. Maintenance: calendar and meters

In a mixed fleet each kind of equipment has its own maintenance logic:

Equipment Maintenance Trigger
Air compressor Oil, air filter, separator, receiver drain, safety valve, operating pressure, belt 12 months or 2,000 run hours, whichever comes first
Pump / booster set Running, leaks, cleaning, electrics and earthing, current, vibration 6 months
Machine The same general list 6 months, or run hours / cycle count
Building systems (automatic doors, barriers, shutters) The same general list, safety devices 6 months

These intervals are industry practice; the right value is in the equipment’s manual. 2,000 hours is a common starting point for compressors, but a screw and a piston compressor, or one running two shifts and one running a single shift, do not deserve the same plan.

This is where meters help. A compressor’s or forklift’s run hours, or the cycle count of a press or packing machine, show when maintenance is due better than the calendar does. Make the reading a required item on the compressor checklist. A reading cannot be lower than the last one; if the meter was replaced, the reading is marked as a reset. We covered readings and thresholds in detail in the generator guide; the same rules apply to compressors and forklifts.

Two compressor items not to skip: safety valve sealed and intact (with a photo) and operating pressure. The operating pressure must stay below the maximum working pressure; take that limit from the maximum pressure field on the equipment record.

5. The inspection record: dates, report and test values

Every pressure vessel and piece of lifting equipment has two dates: the yearly inspection and the three-yearly hydrostatic or load test. Track them separately. If the yearly report does not say a load test was done, the three-year clock keeps running.

What the record should show without opening the report:

  • Inspection date, company, inspector, profession and EKİPNET registration number
  • Report number and the method or standard used
  • Result: pass, pass with minor defects, fail; fit for use or not
  • Minor and major defects
  • For pressure vessels, the hydrostatic test pressure and the safety valve set pressure
  • For lifting equipment, the test load and the operating capacity
  • Next due date and the report file

Every defect should become a work order. We walked through an example in the electrical panels guide; the same routine works for a forklift’s hydraulic leak or a boiler’s safety valve.

6. One template, a mixed fleet

All of this equipment belongs in the same system, but under different types. A forklift’s capacity, drive and mast height; a pressure vessel’s type, maximum and working pressure, volume and last hydrostatic test date; a booster set’s flow, head and pump count are different fields. Sorting equipment into types turns questions such as “every pressure vessel due this month” or “forklifts with a load test coming up” into a list.

If a food factory or a hotel also runs kitchen, HVAC or generator equipment, industry templates can be combined, and the same equipment type is never created twice.

How this works in Saha

The General Technical Service template in Saha comes with types for devices, machines, pumps and booster sets, air compressors, pressure vessels, forklifts and pallet trucks, cranes and hoists, and building systems, with the fields above. If your sector is not on the list, start from this template and add your own equipment types and custom fields. Your existing equipment list can be imported from Excel.

The pre-use operator check is recorded straight on the equipment as a readings log, without a work order; since it is expected daily, a missed day shows as overdue on the equipment. The template includes general maintenance and compressor maintenance checklists and a “12 months or 2,000 hours” plan for compressors. Any piece of equipment can have a run hours meter, a cycle counter or a meter type of your own; readings come in from the web, the iOS and Android apps (offline too), when a work order is completed, or through an Excel import.

Pressure vessel and lifting equipment inspections come as inspection types, with separate plans for the yearly inspection, the three-yearly hydrostatic test and the load test. An inspection record holds the report fields the regulation lists and the type’s own fields (test pressure, safety valve setting, test load, operating capacity). Template plans arrive switched off, so you review them and turn them on. Upcoming and overdue inspections show in the same list as maintenance, and everything lands in the equipment’s service history.

A quick review

  • Is the operator’s daily check recorded on the equipment, and does a missed day show?
  • Are maintenance, the yearly inspection and the three-yearly tests tracked separately?
  • Is compressor and forklift maintenance tied to run hours?
  • Does every pressure vessel have its maximum pressure and last hydrostatic test date on record?
  • Has every defect in the inspection report become a work order?

In a mixed fleet the problem is rarely that maintenance is not done; it is that nobody can see in one place who did what and when. Saha is free for 60 days with no card required; create an account and add your first forklift or compressor.